Inspection Status: Canceled
Inspection History: COT - RSME - Mechanical Final
| Date |
Description |
Inspector |
Results |
Comments |
| 11/04/2022 |
COT - RSME - Mechanical Final |
|
Canceled |
Inspection Canceled |
| 11/30/2023 |
COT - RSME - Mechanical Final |
|
Not Ready |
11/30/2023. Not ready. Missing receptacles at kitchen countertops per code. Add receptacles in bedroom due to them being over 12'. Open neutral in first unit living room. Exhaust fan not working in first unit. Exterior receptacles are not WR and gfci. Laundry room receptacle also needs to be gfci in both units. Change of address needs to be corrected. |
| 12/01/2023 |
COT - RSME - Mechanical Final |
|
Re-inspection required |
Label electrical panel. Exterior receptacles need to be gfci. Provide anti siphon hose bib. Add receptacle at counter top. Bathroom receptacle not functioning. Provide 2nd circuit at kitchen receptacles. 12/1/2023 |
| 12/04/2023 |
COT - RSME - Mechanical Final |
|
Passed |
|