Inspection History Details
Inspection Status: Canceled
Inspection History: COT - RSME - Mechanical Final
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/04/2022 | COT - RSME - Mechanical Final | Canceled | Inspection Canceled | |
| 01/10/2024 | COT - RSME - Mechanical Final | Canceled | 1/10/24: canceled per contractor | |
| 02/12/2024 | COT - RSME - Mechanical Final | Re-inspection required | Tried calling left a voicemail got to the site and no one was there for inspection. Need access to site. 2/12/2024 | |
| 02/27/2024 | COT - RSME - Mechanical Final | Re-inspection required | 1/10/24: canceled per contractor Tried calling left a voicemail got to the site and no one was there for inspection. Need access to site. 2/12/2024 2/27/24: YWL must be insulated, Outdoor receptacles must be WR, 2 circuits required at kitchen, water hammer arrestor required for dishwasher, water hammer missing at laundry room, receptacle at laundry room must be GFCI, receptacle missing at kitchen counter tops (spans are greater than 4'), receptacles at counter top under eave are greater than 12" from top and eave is greater than 6", water heater needs cover properly installed, back patio outdoor lights have no power, upstairs balcony no power at exterior light, no roof access. Garage bay missing another receptacle, GFCI receptacle missing under kitchen sink. STOPPED INSPECTION MORE ITEMS MAY BE ADDED. |
|
| 03/15/2024 | COT - RSME - Mechanical Final | Not Ready | ||
| 03/20/2024 | COT - RSME - Mechanical Final | Re-inspection required (with fee) | ||
| 04/05/2024 | COT - RSME - Mechanical Final | Re-inspection required | ||
| 04/23/2024 | COT - RSME - Mechanical Final | Passed |