Permit: T21CM01303

Parcel: 122173090

Inspection Status: Canceled

Inspection History: COT - LCME - Mechanical Final 

Permit Number - T21CM01303

Inspection Description - COT - LCME - Mechanical Final 

Inspection Status - Canceled

Date Description Inspector Results Comments
11/04/2022 COT - LCME - Mechanical Final  Canceled Inspection Canceled
07/09/2024 COT - LCME - Mechanical Final  Re-inspection required 7/9/24: Arc-fault breaker's missing throughout, high loop at dishwasher not installed properly throughout, water heater pans must be capped, water heater supply line must be insulated. UV coat all exterior plastic piping, access panels missing throughout, properly label HVAC units, water closet's require 15" clearance on sides. Water heater clearances not met in close closet, ensure all fittings are CPVC at T&P discharge Walked all of south apartment. Found items listed above. Walked only first floor of north apartment found same items listed above.
07/11/2024 COT - LCME - Mechanical Final  Passed
09/17/2024 COT - LCME - Mechanical Final  Not Ready Added to permit to allow scheduling when ready.
12/31/2024 COT - LCME - Mechanical Final  Passed