Inspection History Details
Inspection Status: Passed
Inspection History: COT - LCME - Kitchen Hood
Permit Number - T21CM01085
Inspection Description - COT - LCME - Kitchen Hood
Inspection Status - Passed
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/08/2022 | COT - LCME - Kitchen Hood | JBURGE | Approved | Entered by NGARCIA3 - Approved. Annul fire suppression system tested and approved. |
09/07/2022 | COT - LCME - Kitchen Hood | JBURGE | Not ready for Inspection | Entered by VVERA1 - Not ready. Need Fire,Hood Final. |
07/29/2022 | COT - LCME - Kitchen Hood | JBURGE | Partial Approval | Entered by NGARCIA3 - Partial. New access door added to duct system. Ok to insulate. |
07/19/2022 | COT - LCME - Kitchen Hood | WGALLAGHER | Partial Approval | Entered by NGARCIA3 - Partial approval for 1st and 2nd wrap, please add access plate in horizontal duct along south wall in center of duct length |
07/18/2022 | COT - LCME - Kitchen Hood | WGALLAGHER | Partial Approval | Entered by VVERA1 - Partial approval 1 leak in duct marked, ok to wrap exhaust duct, partial approval for 2 wraps through truss area to Exhaust fan |
07/15/2022 | COT - LCME - Kitchen Hood | TLUNDBERG | Cancelled | Entered by NGARCIA3 - CA per Jason |
07/12/2022 | COT - LCME - Kitchen Hood | WGALLAGHER | Partial Approval | Entered by NGARCIA3 - Partial approval smoke test of all hood duct sections ok to proceed |