Inspection Status: Passed
Inspection History: COT - LCME - Kitchen Hood
| Date |
Description |
Inspector |
Results |
Comments |
| 09/08/2022 |
COT - LCME - Kitchen Hood |
JBURGE |
Approved |
Entered by NGARCIA3 - Approved. Annul fire suppression system tested and approved. |
| 09/07/2022 |
COT - LCME - Kitchen Hood |
JBURGE |
Not ready for Inspection |
Entered by VVERA1 - Not ready. Need Fire,Hood Final.
|
| 07/29/2022 |
COT - LCME - Kitchen Hood |
JBURGE |
Partial Approval |
Entered by NGARCIA3 - Partial. New access door added to duct system. Ok to insulate.
|
| 07/19/2022 |
COT - LCME - Kitchen Hood |
WGALLAGHER |
Partial Approval |
Entered by NGARCIA3 - Partial approval for 1st and 2nd wrap, please add access plate in horizontal duct along south wall in center of duct length |
| 07/18/2022 |
COT - LCME - Kitchen Hood |
WGALLAGHER |
Partial Approval |
Entered by VVERA1 - Partial approval 1 leak in duct marked, ok to wrap exhaust duct, partial approval for 2 wraps through truss area to Exhaust fan |
| 07/15/2022 |
COT - LCME - Kitchen Hood |
TLUNDBERG |
Cancelled |
Entered by NGARCIA3 - CA per Jason |
| 07/12/2022 |
COT - LCME - Kitchen Hood |
WGALLAGHER |
Partial Approval |
Entered by NGARCIA3 - Partial approval smoke test of all hood duct sections ok to proceed |