Inspection History: COT - RSEL - Electrical Final
Permit Number - T21CM01079
Inspection Description - COT - RSEL - Electrical Final
Inspection Status - Canceled
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/07/2022 | COT - RSEL - Electrical Final | Canceled | Inspection Canceled | |
03/24/2022 | COT - RSEL - Electrical Final | DMUNIZ | Denied | Entered by VVERA1 - Denied, Main panel does not have a main disconnect and has more than 6 breakers. Service entrance conductors are damaged and need to be replaced. Bond all electrical enclosures and install bond bushings for raceways. |
10/18/2021 | COT - RSEL - Electrical Final | DQUINN | Cancelled | Entered by RSALDAT1 - |
10/01/2021 | COT - RSEL - Electrical Final | TGAUSP | Denied | Entered by NGARCIA3 - Denied, installation not per approved plans |