Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/16/2021 | PLUMBING - GAS PRESSURE TEST | Approved | APPROVED | |
| 02/12/2021 | PLUMBING - GAS PRESSURE TEST | Denied | DENIED - Grease and tape all threaded joints. Disconnect from meter, cap pipe, and place pressure test with 15 lb gauge, noting the starting pressure of at least 10lbs, preferably 15. |