Permit: T21CM01014

Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Permit Number - T21CM01014

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/28/2021 FIRE - ALARM FINAL Approved
07/26/2021 FIRE - ALARM FINAL Partial Approval -submit as-built plans
-install breaker lock on FACP power supply
-submit ROC paperwork