Inspection History Details
Inspection Status: Canceled
Inspection History: COT - FCON - Fire - Final
Permit Number - T21CM00886
Inspection Description - COT - FCON - Fire - Final
Inspection Status - Canceled
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/07/2022 | COT - FCON - Fire - Final | Canceled | Inspection Canceled | |
| 08/18/2022 | COT - FCON - Fire - Final | CGates | Partial Approval | Entered by CGATES1 - OK to obtain TCO until the two-way communication was been installed in the elevator and the elevator has been recommissioned by the state. |
| 07/27/2022 | COT - FCON - Fire - Final | JPEEL-DAVIS | Prior to Final Inspectn | Entered by JPEELDA1 - The fire alarm was approved with two phone and it shall be changed to either a cell or 1 POTS and another means of transmission. Fire alarm shall be retested with new monitoring pior to TCO being obtained. |
| 02/16/2023 | COT - FCON - Fire - Final | Passed | Approved by C Gates on 1/20/2023 |