Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T21CM00606

Parcel: 305977160

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/12/2021 ELECTRIC - FINAL Approved AP receptacle is per approved plans.
10/11/2021 ELECTRIC - FINAL Correction Required correction required, Kitchen island receptacle does not meet requirements per NEC 210.52. Countertop overhang may not exceed 6”, where required GFCI receptacle is installed.