Permit: T21CM00606

Parcel: 305977160

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T21CM00606

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/12/2021 ELECTRIC - FINAL Approved AP receptacle is per approved plans.
10/11/2021 ELECTRIC - FINAL Correction Required correction required, Kitchen island receptacle does not meet requirements per NEC 210.52. Countertop overhang may not exceed 6”, where required GFCI receptacle is installed.