Inspection Status: Canceled
Inspection History: COT - FCON - Fire - Final
| Date |
Description |
Inspector |
Results |
Comments |
| 11/07/2022 |
COT - FCON - Fire - Final |
|
Canceled |
Inspection Canceled |
| 08/15/2022 |
COT - FCON - Fire - Final |
CBASALDUA |
Partial Approval |
Entered by CBASALD1 - 1. Ok for TCO to occupy
2. Need permanent power from TEP
3. Knox Box and keys needed
4. Fix electric bell
5. When BAF are powered, need to verify they shut down upon Fire Alarm activation |