Inspection History Details
Inspection Status: Partial Approval
Inspection History: POOL/SPA FINAL/BARRIER
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/02/2021 | POOL/SPA FINAL/BARRIER | Partial Approval | pa House alarms are in place. Need: 1. Timer installed. 2. Submit revision of heater changes from gas to electric, for review and approval of specifications. 3. Submit name of licensed contractor for the pool permit, before final will be approved. 4. Need complete set of approved plans on site for the final inspection to confirm items like breaker sizes matching to mechanical specifications. |
|
| 08/31/2021 | POOL/SPA FINAL/BARRIER | Partial Approval | pa Need 8035 complete. |
|
| 08/27/2021 | POOL/SPA FINAL/BARRIER | Not ready for Inspection | nr Recall when complete. |