Inspection History Details
Inspection Status: Approved
Inspection History: POOL/SPA FINAL/BARRIER
Permit Number - T21BU00180
Inspection Description - POOL/SPA FINAL/BARRIER
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/01/2022 | POOL/SPA FINAL/BARRIER | Approved | AP | |
12/23/2021 | POOL/SPA FINAL/BARRIER | Partial Approval | Partial, finish equipment install and secure electrical whip. | |
12/20/2021 | POOL/SPA FINAL/BARRIER | Correction Required | CO 1. GFCI pool pump breaker 2. Door to pool sub-panel falls off when opened 3. Install bonding jumper to other side of the pool gate by equipment |