Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T20FC00638
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/25/2021 | FIRE - ALARM FINAL | Approved | ||
02/24/2021 | FIRE - ALARM FINAL | Denied | -Need to verify HVAC units shutdown upon duct detector activation -3 notification devices on the 2nd floor did not work. all the devices on the 3rd floor did not work. -Submit as built plans -Signals were verified with monitoring company -Tamper and flow are approved -smoke and pull at the panel are approved. |
|
09/30/2020 | FIRE - ALARM FINAL | Prior to Final Inspectn | ALL SHARED OFFICES SHALL HAVE NOTIFICATION INSTALLED PROVIDE 1 FULL SIZE SET 24X36 FOR THE JOB SITE PRIOR TO FINAL PROVIDE DBA METER AT FINAL SUBJECT TO FIELD INSPECTION/VERIFICATION |