Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit: T20FC00625

Parcel: 13608032E


Addresses:

2200 S HOUGHTON RD

Inspection Status: Approved

Inspection History: FIRE SPKLR - UG PIPING FLUSH

Date Description Inspector Results Comments
08/30/2022 FIRE SPKLR - UG PIPING FLUSH Approved
07/27/2021 FIRE SPKLR - UG PIPING FLUSH Cancelled to open the permit back open