Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/12/2021 | FIRE - ALARM FINAL | Approved | ||
| 05/11/2021 | FIRE - ALARM FINAL | Partial Approval | Picture of locked out breaker | |
| 02/25/2021 | FIRE - ALARM FINAL | Denied | Pull station activated only some of the notification devices No local alarm at main FACP upon general alarm Verify signals to PBX Verify 2 hour firewall between buildings if notification devices in said buildings operate independently |