Inspection History: FIRE - ALARM FINAL

Permit Number - T20FC00617

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/22/2020 FIRE - ALARM FINAL Approved
12/14/2020 FIRE - ALARM FINAL Partial Approval -HVAC units did not shut down
09/28/2020 FIRE - ALARM FINAL Prior to Final Inspectn Fire alarm shall be labeled as a dedicated function water flow and supervisory system per NPFA 72
Provide document can per NFPA 72
Please print 1 full size set of drawings for the job site
Provide dBA meter at final
Confirm that the AES communication failure and power loss report to the fire alarm panel