Permit: T20FC00575

Parcel: 13014009D


Addresses:

4380 E 22ND ST

Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Date Description Inspector Results Comments
01/14/2021 FIRE - ALARM FINAL Approved
01/07/2021 FIRE - ALARM FINAL Partial Approval 1. Tested all devices and notifcation that was installed including water flow, tamper, pull stations, hood switches, and FACP smoke. All passed and reported.
2. Need to add 3 devices in walk in coolers per plans.