Inspection History Details
Inspection Status: Partial Pass
Inspection History: COT - FCON - Alarm - Final
Permit Number - T20FC00495
Inspection Description - COT - FCON - Alarm - Final
Inspection Status - Partial Pass
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/05/2021 | COT - FCON - Alarm - Final | CBASALDUA | Partial Approval | Entered by CBASALD1 - Tested Water Flows and Tampers. All reporting to panel. |
01/14/2021 | COT - FCON - Alarm - Final | jfordney | Denied | Entered by JFORDNE1 - Tamper and waterflow not reporting to panel correctly re-inspection fee will be added |
01/07/2021 | COT - FCON - Alarm - Final | IVR USER | Cancelled | Entered by IVR USER - IVRS - RI canceled |
11/05/2020 | COT - FCON - Alarm - Final | jfordney | Denied | Entered by JFORDNE1 - Need to test heat and smoke detectors in elevator shaft Ensure all magnetic doors function properly and close completely Submit as builts FACP sign Document box with plans Still need to verify tamoers, water flow, A/C drop, DC, ground fault Verify location of smokes 105,321,325,329,233, south stairwell 1st and 3rd floor Report location elevator mechanical room, not mechanical room. re-inspection fee will be added |