Permit: T20FC00487

Parcel: 141019150


Addresses:

10425 E DREXEL RD


Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Permit Number - T20FC00487

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/23/2020 FIRE - ALARM FINAL Approved
10/21/2020 FIRE - ALARM FINAL Denied Need "as builts"
AC power loss smoke must report correctly to central station
Verify dispatch phone number
Recordof completion
Re-inspection fee added
07/28/2020 FIRE - ALARM FINAL Prior to Final Inspectn * SUBJECT TO FIELD VERIFICATION
* PANEL SHALL BE LABELED PER NFPA 72 - DEDICATED FUNCTION "SPRINKLER WATERFLOW AND SUPERVISORY SYSTEM"
* PER NFPA 72 DRAWINGS SHALL ALSO REFELECT THAT THIS IS A DEDICATED FUNCTION FIRE ALARM SUBMIT AS BUILT DRAWINGS.
* PROVIDE REQUIRED NFPA DOCUMENT CABINET
* PLEASE PRINT 1 FULL SIZE SET OF THE DRAWINGS FOR THE JOB SITE PRIOR TO FINAL.