Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/04/2021 | FIRE - ALARM FINAL | Approved | P2F ROC | |
| 06/03/2021 | FIRE - ALARM FINAL | Cancelled | IVRS - RI canceled | |
| 05/13/2021 | FIRE - ALARM FINAL | Denied | RTU 23 did not shut down after duct smoke activtion RTU 8 shut down but was not received by central station All other signals good Reinspection fee added. |
|
| 04/28/2021 | FIRE - ALARM FINAL | Cancelled | Target didn't want to set off alarm during business hours. | |
| 02/09/2021 | FIRE - ALARM FINAL | Not ready for Inspection | Doors to be tied into alarm not in yet. reinspection fee to be added |