Inspection Status: Canceled
Inspection History: COT - FCON - Alarm - Final
| Date |
Description |
Inspector |
Results |
Comments |
| 11/07/2022 |
COT - FCON - Alarm - Final |
|
Canceled |
Inspection Canceled |
| 01/12/2021 |
COT - FCON - Alarm - Final |
Mross |
Partial Approval |
Entered by MROSS2 - -Tested and verified the following signals
-Pull station
-Smoke above panel
-Tamper valve
-Waterflow
-Ansul system
CO2 monotoring system was not tested. Contractor rep was not on site to test .
-Submit NFPA 72 ROC when CO2 system test is complete |
| 07/21/2020 |
COT - FCON - Alarm - Final |
JPEELDAVIS |
Cancelled |
Entered by JPEELDA1 - * BUILDING NOTES SHOW THAT THEY HAVE A KITCHEN FIRE SUPPRESSION SYSTEM THAT WILL ALSO NEED TO BE CONNECTED TO THE FACP
* PANEL TO BE SIGNED AS A DEDICATED FUNCTION PER NFPA 72
* PROVIDE REQUIRED NFPA 72 DOCUMENT BOX
* PLEASE PRINT 1 FULL SIZE SET FOR THE JOB |