Inspection History Details
Inspection Status: Canceled
Inspection History: COT - FCON - Alarm - Final
Permit Number - T20FC00384
Inspection Description - COT - FCON - Alarm - Final
Inspection Status - Canceled
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/07/2022 | COT - FCON - Alarm - Final | Canceled | Inspection Canceled | |
01/12/2021 | COT - FCON - Alarm - Final | Mross | Partial Approval | Entered by MROSS2 - -Tested and verified the following signals -Pull station -Smoke above panel -Tamper valve -Waterflow -Ansul system CO2 monotoring system was not tested. Contractor rep was not on site to test . -Submit NFPA 72 ROC when CO2 system test is complete |
07/21/2020 | COT - FCON - Alarm - Final | JPEELDAVIS | Cancelled | Entered by JPEELDA1 - * BUILDING NOTES SHOW THAT THEY HAVE A KITCHEN FIRE SUPPRESSION SYSTEM THAT WILL ALSO NEED TO BE CONNECTED TO THE FACP * PANEL TO BE SIGNED AS A DEDICATED FUNCTION PER NFPA 72 * PROVIDE REQUIRED NFPA 72 DOCUMENT BOX * PLEASE PRINT 1 FULL SIZE SET FOR THE JOB |