Permit: T20FC00359

Parcel: 12513068B

Inspection Status: Canceled

Inspection History: FCON – OH Piping & Hydro

Date Description Inspector Results Comments
11/07/2022 FCON – OH Piping & Hydro Canceled Inspection Canceled
10/25/2021 FCON – OH Piping & Hydro jpeeldavis Cancelled Entered by JPEELDA1 -
10/04/2021 FCON – OH Piping & Hydro MRoss Partial Approval Entered by MROSS2 - Inspection 26 - Parking garage, level 1, partial approval
08/09/2021 FCON – OH Piping & Hydro MRoss Partial Approval Entered by MROSS2 - Inspection 25 - Level 2, Seahawks building
07/26/2021 FCON – OH Piping & Hydro MRoss Partial Approval Entered by MROSS2 - Inspection 24 - Level 3, north building Seahawks. partianl approval
07/08/2021 FCON – OH Piping & Hydro MRoss Partial Approval Entered by MROSS2 - Inspection 23 - Level 3 Miami
06/24/2021 FCON – OH Piping & Hydro MRoss Partial Approval Entered by MROSS2 - Inspection 22 - parking garage level 2 Seahawks & Retail level 1 Miami
06/21/2021 FCON – OH Piping & Hydro MRoss Partial Approval Entered by MROSS2 - Inspection 21 - Miami building. 2nd floor
05/28/2021 FCON – OH Piping & Hydro jfordney Partial Approval Entered by JFORDNE1 - Inspection 20 North building Floors 4, 5 and attic north of elevator. P2F ensure insulation doesn't obstruct any sprinkler heads
05/05/2021 FCON – OH Piping & Hydro MRoss Partial Approval Entered by MROSS2 - Inspection 19 - Vikings & Steelers buildings floors 2 & 3
04/07/2021 FCON – OH Piping & Hydro MRoss Partial Approval Entered by MROSS2 - Inspection 18 - 1st floor, north building, Eagles, Vikings, Steelers.
03/25/2021 FCON – OH Piping & Hydro MRoss Partial Approval Entered by MROSS2 - Inspection 17 - Eagles bldg 3rd & 4th floor. Rms 3339 & 3340 bedrooms have dropped ceilings, need to adjust heads. 3rd floor hall in front of stairs, 2 heads too close together.
03/16/2021 FCON – OH Piping & Hydro wmotto1 Partial Approval Entered by WMOTTO1 - ohpt 210 psi at the gauge for the horizonal standpipes at the north building.
03/11/2021 FCON – OH Piping & Hydro jfordney Partial Approval Entered by JFORDNE1 - Eagle bldg Floor 1 approved south of 3105. (3105 not done) Eagle bldg floor 2 stairwell hallway needs coverage Eagle bldg floor 2 Approved from south side to breezeway
02/18/2021 FCON – OH Piping & Hydro MRoss Partial Approval Entered by MROSS2 - Inspection 14 -Broncos Floor 4 & attic space
02/11/2021 FCON – OH Piping & Hydro MRoss Partial Approval Entered by MROSS2 - Inspection 13- Broncos Floor 3, Dallas Floor 4/5
01/26/2021 FCON – OH Piping & Hydro Mross Partial Approval Entered by MROSS2 - Inspection 12 - Broncos floor 2, Rm 2231 missing head in hall closet. Rm 2225 living rm head is dripping. Cardinals bldg floor 4/5 - all rooms ok.
01/19/2021 FCON – OH Piping & Hydro Mross Partial Approval Entered by MROSS2 - Inspection 11 - Broncos Floor 1, partial 4th floor, 4 more 2 story units, (now have 8 completed)
01/07/2021 FCON – OH Piping & Hydro Mross Partial Approval Entered by MROSS2 - Inspection 10 - Dallar bldg Floor 3. Cardinal bldg 4th floor 4 north units
12/23/2020 FCON – OH Piping & Hydro MRoss Partial Approval Entered by MROSS2 - Inspection 9 - Dallas bldg, Floor 2, Partial Approval. Room 2216 has small drip in kitchen soffit.
12/16/2020 FCON – OH Piping & Hydro MRoss Partial Approval Entered by MROSS2 - Inspection 8 - Dallas bldg, Floor 1 - residential areas South attic (level 5) - room 2417 missing an upright head.
11/23/2020 FCON – OH Piping & Hydro MRoss Partial Approval Entered by MROSS2 - -Inspection 7 - Cardinals bldg, Floor 3
11/19/2020 FCON – OH Piping & Hydro MRoss Partial Approval Entered by MROSS2 - -Inspection 6 - Cardinals bldg, Floor 2 partial approval
10/28/2020 FCON – OH Piping & Hydro MRoss Partial Approval Entered by MROSS2 - Inspection 5 - Cardinals bldg, Floor 1 Partial approval
10/26/2020 FCON – OH Piping & Hydro MRoss Denied Entered by MROSS2 - Inspection 4 - Cardinals bldg, 1st floor, leak at fitting in room 2113.
10/20/2020 FCON – OH Piping & Hydro MRoss Partial Approval Entered by MROSS2 - -Inspection 3 - Green Bay bldg Floor 3 - partial approval
10/05/2020 FCON – OH Piping & Hydro MRoss Partial Approval Entered by MROSS2 - -Inspection 2 - Green Bay bldg Floor 2 - Partial approval -Veriy sidewall coverage in living space off of kitchen. distance to wall in 20'6". Sidewall on legend is F1Res44 which has a max coverage of 16x20
09/28/2020 FCON – OH Piping & Hydro MRoss Partial Approval Entered by MROSS2 - Instpection 1 - Green Bay bldg Floor 1 - partial approval