Permit: T20FC00297

Parcel: 14002010A


Addresses:

3950 E IRVINGTON RD


Inspection Status: Approved

Inspection History: FIRE SPKLR - UG, PIPING, HYDRO

Permit Number - T20FC00297

Inspection Description - FIRE SPKLR - UG, PIPING, HYDRO

Inspection Status - Approved

Date Description Inspector Results Comments
05/26/2021 FIRE SPKLR - UG, PIPING, HYDRO Approved
01/07/2021 FIRE SPKLR - UG, PIPING, HYDRO Partial Approval Intermediate building riser and 10' of pipe 215 PSI
08/19/2020 FIRE SPKLR - UG, PIPING, HYDRO Not ready for Inspection last 50' of pipe to hydrant on NE corner of existing building not in yet.
07/08/2020 FIRE SPKLR - UG, PIPING, HYDRO Partial Approval Observed 60' from main east to first 90* turn.
06/30/2020 FIRE SPKLR - UG, PIPING, HYDRO Partial Approval 208 PSI for 2 hours.
Still need to see 4" and 6" lines that head east to building under pressure.
06/29/2020 FIRE SPKLR - UG, PIPING, HYDRO Cancelled Spoke with Noberto from Kazal, he said he did not have an inspection for today.
06/26/2020 FIRE SPKLR - UG, PIPING, HYDRO Partial Approval -Observed tie in to 4" on NW side of existing OH building
-Observed 100' of 6" to hydrant on north side of existing OH building
-Observed 55' of 6" from 6"tee to hydrant on west side of property next to the road
06/23/2020 FIRE SPKLR - UG, PIPING, HYDRO Partial Approval From 80' south of 6" tee to northwest corner of existing OH building,
6" is reduced to 4" 60' from building.
06/17/2020 FIRE SPKLR - UG, PIPING, HYDRO Partial Approval Inspected from second 45 degree turn to 80' past 6" T that went east toward building. Inpection done via Facetime.
06/17/2020 FIRE SPKLR - UG, PIPING, HYDRO Partial Approval 240' of fire line on North side of project was inspected and then buried. TFD did not see this portion under pressure, GRANITE TO ACCEPT FULL RESPONSIBILTY AND LIABILITY FOR UNDERGROUND FIRE LINES AS TFD WILL NOT WITNESS ALL HYDRO TESTS. 6/10/2020
We saw 70ft to the hydrant as well as the T that goes south 6/12/2020
through both 45 degree turns heading south 6/17/2020
06/16/2020 FIRE SPKLR - UG, PIPING, HYDRO Not ready for Inspection The trench was dug, however there was no pipe installed to inspect