Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T20FC00217
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/26/2020 | FIRE - ALARM FINAL | Approved | verifed all signals from BDA to FACP verified BDA coverage for entire building |
|
05/20/2020 | FIRE - ALARM FINAL | Denied | Move the annunciator by the FACP in the IDF room. Need to have testing equipement in order to test BDA. Still awaiting the FM approval for the equipement. |