Inspection History: FIRE - ALARM FINAL

Date Description Inspector Results Comments
04/24/2020 FIRE - ALARM FINAL Approved Record of copletion in FRMS
04/23/2020 FIRE - ALARM FINAL Denied 1. No one on site at 12:00pm. No messages or call back number. Contacted Climatec in the AM, was informed a call from a tech. No call back.
04/14/2020 FIRE - ALARM FINAL Denied 1) Duct Smoke Detectors shall be supervisory not alarm
2) Smoke west area sgall be removed and relocated to 3' from air supply
3) all low voltage shall be removed
4) label AHU test units
5) Locate breaker and lock out per NFPA 72
6) AES & Starlink shall cause comm fail to the FACP
7) Fees will be added and shall be paid prior to closing out the permit
8) JBox covers need to be installed