Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T20FC00113
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/05/2020 | FIRE - ALARM FINAL | Approved | Seth Dykstra verified signals | |
04/22/2020 | FIRE - ALARM FINAL | Denied | -SIGNAL NOT RECEIVED BY CENTRAL STATION -RECORD OF COMPLETION REQUIRED AT FINAL. |
|
04/21/2020 | FIRE - ALARM FINAL | Cancelled | IVRS - AP canceled | |
02/28/2020 | FIRE - ALARM FINAL | Partial Approval | - Fire alarm devices need to synchronize -Add notification to MA ststion -Add notification to reception area -Provide as built drawings -Need to test duct smoke detectors - |
|
02/27/2020 | FIRE - ALARM FINAL | Compliance | NEED TO ADD 6 NOTIFICATION DEVICES TO THE EXAM ROOMS AND SUBMIT ASBUILT DRAWINGS PRIOR TO CALLING IN FIRE ALARM FINAL | |
02/27/2020 | FIRE - ALARM FINAL | Cancelled | IVRS - AP canceled |