Inspection History: FIRE - ALARM FINAL

Permit Number - T20FC00113

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/05/2020 FIRE - ALARM FINAL Approved Seth Dykstra verified signals
04/22/2020 FIRE - ALARM FINAL Denied -SIGNAL NOT RECEIVED BY CENTRAL STATION
-RECORD OF COMPLETION REQUIRED AT FINAL.
04/21/2020 FIRE - ALARM FINAL Cancelled IVRS - AP canceled
02/28/2020 FIRE - ALARM FINAL Partial Approval - Fire alarm devices need to synchronize
-Add notification to MA ststion
-Add notification to reception area
-Provide as built drawings
-Need to test duct smoke detectors
-
02/27/2020 FIRE - ALARM FINAL Compliance NEED TO ADD 6 NOTIFICATION DEVICES TO THE EXAM ROOMS AND SUBMIT ASBUILT DRAWINGS PRIOR TO CALLING IN FIRE ALARM FINAL
02/27/2020 FIRE - ALARM FINAL Cancelled IVRS - AP canceled