Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T20FC00017
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/25/2020 | FIRE - ALARM FINAL | Approved | approved per Inspector Ross | |
| 02/14/2020 | FIRE - ALARM FINAL | Denied | No inspection conducted. Not ready. Contractor for postinos wanted this called in so RI fees going on CM permit. | |
| 02/12/2020 | FIRE - ALARM FINAL | Denied | -RTUs not wired up to shut down upon smoke duct detector activation -Missing notification device in walk in cooler -Missing notification devices on pation Verified the following devices and signals: -Waterflow -Tamper -Smoke above panel -Pull station at panel |