Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/03/2020 | FIRE - ALARM FINAL | Approved | ||
| 05/22/2020 | FIRE - ALARM FINAL | Partial Approval | -music shall shut down on general alarm per notes on plan from reviewer. -provide 72/ROC -tamper switch not reporting to panel. -AC power loss signal reporting as battery loss. resolve. -incorrect address at central station for this suite. |