Permit: T20EL00003

Parcel: 129040210


Addresses:

2034 E 8TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
01/08/2020 ELECTRIC - RECONNECT Approved
01/07/2020 ELECTRIC - RECONNECT Denied Since this is for construction power only, remove all circuit wires from breakers and tape the ends.
Install raised metal address tag on panel.
Install a 20 amp gfi at the bottom of the panel, with #12 wire to a 20 amp breaker.
Install bonding jumper from bonded gas line to water line. Water bond has been removed.