Case: T20DV07922

Parcel: 11918029D


Addresses:

1310 W AJO WY


Inspection Status: Approved

Inspection History: INSP - INITIAL CODE ENFORCMENT

Case Number - T20DV07922

Inspection Description - INSP - INITIAL CODE ENFORCMENT

Inspection Status - Approved

Date Description Inspector Results Comments
12/13/2020 INSP - INITIAL CODE ENFORCMENT Approved EMERGENCY CALL OUT BY TFD: THERE IS FIRE DAMAGE TO THE 2 X 4 WOOD FRAMING MEMBERS INSIDE THE LAUNDRY ROOM. THE BUILDING IS WOOD FRAME TYPE AND IS DETACHED WITH A POOL ADJACENT. THERE ARE 2 STUDS AND CROSS MEMBERS ARE BURNT AND THEY DO SUPPORT THE EXTERIOR WALL THE OTHER FIRE DAMAGED MEMBERS SUPPORT AND PARTITIONED WALL TO THE ADJACENT STORAGE ROOM. THE IS DRYWALL DAMAGE INSIDE THE LAUNDRY AND STORAGE ROOM


ELECTRICAL: THIS BUILDING IS ALL ELECTRIC, THE DRYERS AND OTHER WALL OUTLETS ARE IN CLOSE PROXIMITY TO THE FIRE. TEP DID DISCONNECT POWER TO THE BUILDING



PLUMBING: N/A



MECHANICAL: VENTILATION PIPING TO THE DRYERS ARE DAMAGED.


REMARKS: PERMITS REQUIRED FOR BUILDING AND ELECTRICAL/MECHANICAL REPAIRS REQUIRED. THE BUILDING WAS SECURED BY THE CITY. NO MANAGEMENT AND OWNERSHIP ONSITE. THE BUILDING WAS CONDEMNED AND POSTED UNSAFE TO OCCUPY