Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Case: T20DV07163

Parcel: 137082350


Addresses:

207 W WEDWICK ST

Inspection Status: Approved

Inspection History: INSP - INITIAL CODE ENFORCMENT

Date Description Inspector Results Comments
10/30/2020 INSP - INITIAL CODE ENFORCMENT Approved The office called that T.F.D. on site with a house fire. Arrived and all the units were cleared and the fire investigator was on site checking for cause. The fire was in a play house and 2-storage rooms. One of the storage room was wood frame with wood siding with a light on the exterior. One of the storage room is metal with metal siding. It had a light on the interior and burned in the area of the light. The play house was wood frame and burned due to the amount of tall grass and weeds with trash and debris in the rear yard area including the alley. The electrical was turned off at the panel due to the electrical was still arcing on the wood frame storage room. The wiring was removed to the breaker that gave power to the 4 x 4 box that fed the lights, outlets and a 220 outlet loose and on the wall in the area. The wiring had no neutral connected and the white wire was being used as a hot leg. The 220 was using the grounding wire as the neutral due to the white wire was a hot leg. RV.