Inspection Status: Approved
Inspection History: INSP - FOLLOW UP CODE ENFORCE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/29/2020 | INSP - FOLLOW UP CODE ENFORCE | Approved | PERMIT T20CM07846 ISSUED, CLOSE COSE | |
| 10/29/2020 | INSP - FOLLOW UP CODE ENFORCE | Approved | ON SITE MEETING WITH MANAGER, SEE DETAILS IN CONDITIONS | |
| 10/29/2020 | INSP - FOLLOW UP CODE ENFORCE | Approved | MET WITH THE ELECTRICAL CONTRACTOR: THE 200 AMP MAGNETIC CONTACTOR HAS FAILED IN PANEL PB, PANEL PB DOES ENERGIZE TYE CANOPY LOGHTING TO THE FUEL STATION. THE POWER WAS DISCONNECTED ON 1-28-2020. THE CITY HAS AUTHORIZED AN EMERGENCY REPAIR AND TO OBTAIN A PERMIT AS SOONS AS POSSIBLE. THE EMERGENCY REPAIR IS DEFINED AS REPLACEMENT OF THE 200 AMP MAGNETIC CONTACTOR. SPECIAL ORDER ARE AS FOLLOWS: THE FUEL STATION SHALL ONLY OPERATE FROM SUN UP TO SUN DOWN. |