Case: T20DV07071

Parcel: 13715144C


Addresses:

2160 W DREXEL RD

Inspection Status: Approved

Inspection History: INSP - INITIAL CODE ENFORCMENT

Date Description Inspector Results Comments
10/28/2020 INSP - INITIAL CODE ENFORCMENT Approved THERE IS A BURN SMELL EMINATING FROM PANEL PB , BREAKERS IN PANEL PA WERE SHUT OFF, THE FOLLOWING BREAKER ARE TO REMAIN OFF,36,38,40,42. A LICENSED ELECTRICIAN IS REQUIRE TO INSPECTED INTERIOR OF THE PANEL AND MAKE REQUIRED REPAIRS. PERMIT WILL BE DETERMINED ON THE SCOPE OF REPAIR. THIS DEFECT AFFECTED THE EXTERIOR CANOPY LIGHTS THE MARKET DID SELF CLOSE.