Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FOLLOW UP CODE ENFORCE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/25/2020 | INSP - FOLLOW UP CODE ENFORCE | Approved | PERMIT T20CM08179 IN PLAN CHECK .. CLOSE CASE | |
| 09/18/2020 | INSP - FOLLOW UP CODE ENFORCE | Approved | THE MAIN SERVICE CONSIST OF THREE SPLIT METER DISCONNECTS 60 AMPS EACH, ALL DISCONNECTS HAVE NO LABELING. 1. THE MAIN HOME'S DISCONNECT HAZARDS ARE AS FOLLOWS: THE 60 AMP CIRCUIT BREAKER HAS NUMBER 6 FEEDERS EXITING THE DISCONNECT AND TRAVEL UNPROTECTED OVER A DISTANCE OF 15 FEET TO THE NEW 200 AMP DISCONNECT, THERE IS SO MUCH SLACK THAT THE FEEDERS ARE COILED MULTIPLE TIMES BEFORE ENTERING THE 200 AMP NEW DISCONNECT BY WAY OF THE METER SOCKET AND CONNECT TO THE BUSBAR, THERE IS A 50 AMP CIRCUIT BREAKER WITH FEEDERS WHICH TRAVEL UNDERGROUND VIA PVC CONDUIT AND ENTER A NEW 125 AMP PANEL WHICH ENERGIZES MULTIPLE BRANCH CIRCUITS TO THE MAIN HOME. "THE MAIN HOMES DISCONNECT CODE VIOLATIONS AS FOLLOWS: " NO DEAD FRONT " NO LABELING " THE 30 AMP OVER CURRENT PROTECTION DEVICE EXCEEDS THE AMPACITY OF THE FEEDERS " UNAPPROVED WIRING METHODS " MISSING CONNECTORS " UNPROTECTED FEEDERS " NEUTRAL CONDUCTOR BEING USED AS A HOT CONDUCTOR " STRAND WIRE FEEDERS ENTERS CIRCUIT BREAKER WITH CUT ENDS " 30 AMP CIRCUIT BREAKER HAS UF CABLE WHICH ENTERS ADJACENT MAIN DISCONNECT TO FEED UNKNOWN DESTINATIONS " CONDUIT AND CONNECTORS ARE DAMAGED AND UNSECURED WITH EXPOSED CONDUCTORS 2. MAIN DISCONNECT IS WEST OF THE CENTER DISCONNECT WHICH IS THE MAIN HOME DISCONNECT " NO DEAD FRONT " NO LABELING " DISCONNECT BEING USED AS A JUNCTION BOX " UNUSED OPENINGS " UF CABLE FROM ADJACENT DISCONNECT IS ENERGIZING MULTIPLE CONDUCTORS, UNKNOWN DESTINATIONS. 3. MAIN DISCONNECT EAST OF THE HOME'S DISCONNECT " NO DEAD FRONT " NO LABELING " 7 CIRCUIT BREAKER IN OPERATION, NO MAIN BREAKER " UNUSED OPENINGS " UNSECURED CONDUIT WITH EXPOSED CONDUCTORS " CONNECTOR IS BROKEN WITH EXPOSED CONDUCTORS 4. 125 AMP PANEL " NO PERMIT FOR THIS INSTALL " FEEDERS ENTERING THE DISCONNECT VIA CONDUIT NO BUSHING (PROTECTION) " LARGE PENETRATION WHERE BRANCH CIRCUITS ENTER THE HOME, NOT SEALED " LOAD CALCULATION REQUIRED. " ACCESS AND CLEARANCE VIOLATIONS TO EQUIPMENT 5. ILLEGAL RV " SQUATTER LIVING IN THE RV " BEING POWERED BY AN EXTENSION CORD WHICH CONNECTS TO ANOTHER SLICED CORD. " MULTIPLE SITE VISITS FROM TPD DUE TO SQUATTERS AND ARRESTS MADE ONSITE " NO OVERSITE FROM THE OWNER OVERALL: HISTORY: THERE ARE EXPIRED PERMITS SINCE 2016 FOR ELECTRICAL WORK. CURRENTLY THERE WERE TWO NEW PANELS ENERGIZED WITHOUT A PERMIT IN A HAZARDOUS MANNER. THERE IS A 600 AMP 4 METER SOCKET DISCONNECT INSTALL BUT NOT ENERGIZED. THE POWER WAS DISCONNECTED DUE TO THE HAZARDOUS CONDITIONS. THE SYSTEM IS UNSAFE AND IN ITS CURRENT STATE CAN CAUSE ELECTROCUTION .THIS HAZARD IS WITHIN REACH OF A PERSON. THE CURRENT SYSTEM HAS MULTIPLE AREAS OF EXPOSED ENERGIZED FEEDERS PROVIDING POWER TO AN UNPERMITTED 200 AMP DISCONNECT WHICH PROVIDES POWER TO ANOTHER UNPERMITTED 125 PANEL. ALL UNITS ARE CONDEMNED, POWER HAS BEEN DISCONNECTED TO THE SERVICE BY TEP. NOTICE AND ORDER SIGNED BY THE OWNER, PERMIT REQUIRED. |