Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FOLLOW UP CODE ENFORCE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/31/2020 | INSP - FOLLOW UP CODE ENFORCE | Approved | PERMIT T20SA00256 IS APPROVED. CLOSE CASE. | |
| 09/18/2020 | INSP - FOLLOW UP CODE ENFORCE | Approved | ONSITE INSPECTION: THE BRANCH CIRCUIT LABELED FOOD TRAILER HAS AN OVERCURRENT PROTECTION OF 100 AMPS' CIRCUIT BREAKER WITH NUMBER 8 FEEDERS. ZERO DAYS: THE BRANCH CIRCUIT HAS BEEN TURNED OFF AND TO REMAIN OFF. 30 DAYS TO OBTAIN A PERMIT FOR THE BRANCH CIRCUIT MY NOTICE AND ORDER WAS ISSUED ONSITE AND SIGNED BY MANAGEMENT. THE ORDER DOES AUTHORIZE A LICENSED ELECTRICIAN TO CONDUCT AN EMERGENCY REPAIR AND MAKE THAT BRANCH CIRCUIT SAFE: REDUCING THE OVERCURRENT PROTECTION SO THE THAT FEEDERS AND THE CORD CABLE ARE PROTECTED IS THE ONLY OPTION. NO PERMIT REQUIRED FOR THE EMERGENCY REPAIR AS OUTLINED IN THIS EMAIL. |