Inspection History Details
Inspection Status: Approved
Inspection History: INSP - INITIAL CODE ENFORCMENT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/07/2020 | INSP - INITIAL CODE ENFORCMENT | Approved | ONSITE INSPECTION FOUND CONTRACTORS WORKING, THE MAIN HOME HAS THE BATHROOM, KITCHEN GUTTED, BEARING INTERIOR WALLS HAVE BEEN REMOVED, NO INTERIOR WALL AND CEILING COVERING, NO ELECTRICAL, NO FIXTURES. THERE ARE INTERIORS WALL WITH DAMAGE. THE KITCHEN / DINNING ROOM HAS 4 JACKS AND SCAFFOLDING BOARDS SUPPORT THE ROOF LOAD BY WEDGING THE BOARDS UNDER THE ROOF MEMBERS, DUE TO LOAD BEARING INTERIOR WALLS REMOVED. ALL INTERIOR WIRING KNOB AND TUBE HAVE BEEN REMOVED FROM THESE AREAS, THERE ARE SOME WIRING WITH CUT ENDS, THE ELECTRICAL DISCONNECT HAS OPEN EXPOSED FEEDERS ENERGIZED. THE REAR ATTACHED PATIOS HAVE BEEN DEMOLISHED, THE TWO REAR DOOR OPENINGS TO THE KITCHEN AND BASEMENT HAVE BEEN REMOVED. WORKERS HAVE BEGUN WORK TO THE REAR TWO STORY BUILDING, ELECTRICAL ENCLOSURES WITH EXPOSED WIRING AND THE GROUNDS HAVE A DISCONNECT AND CONDUCT WITH WIRE JUST THROWN AND THE DIRT, UNKNOWN WHERE IT WAS REMOVED FROM. TEP WAS CALLED TO DISCONNECT POWER, KMS TO SECURE THE BUILDINGS. STOP WORK ORDER POSTED BOTH UNIT WERE CONDEMNED. THIS BUILDING IS UNSAFE AND UNPERMITTED |