Inspection History: INSP - INITIAL CODE ENFORCMENT

Case Number - T20DV02355

Inspection Description - INSP - INITIAL CODE ENFORCMENT

Inspection Status - Approved

Date Description Inspector Results Comments
04/09/2020 INSP - INITIAL CODE ENFORCMENT Approved EMERGENCY CALL OUT: THERE IS FIRE DAMAGE A BROKEN 3 X 4 WINDOW AND A 4X6X12 FOOT BEAM USE TO SUPPORT A RACEWAY.


ELECTRICAL: TWO RACEWAY WERE UNDER THE FIRE, THESE RACEWAYS ARE 1 ½ FROM THE CURRENT 200 AMP SERVICE AND THE OTHER IS A 2 INCH IS FROM THE NEW 600 AMP SERVICE. THE 1 ½ RACEWAY COMES FROM THE MAIN 200 AMP DISCONNECT AND FEEDS DOWNSTREAM PANELS. TEP IS DISCONNECT POWER, THEY REMOVED THE METER.


PLUMBING: NA


MECHANICAL: UNIT 10 WITH HE BROKEN WINDOW DOES HAVE MILD SMOKE.


REMARKS: THE ENTIRE COMPLEX IS CONDEMNED. OWNER WAS ONSITE AND WAS ADVISED TO HIRE ELECTRICAL CONTRACTOR TO MAKE EMERGENCY REPAIRS UNDER PERMITS, ALL UNITS WERE POSTED UNSAFE TO OCCUPY.