Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/22/2021 | MECHANICAL - FINAL | Approved | Approved. | |
| 09/13/2021 | MECHANICAL - FINAL | Denied | De Inspection was stopped when it became apparent that all trades were incomplete or had deficiencies. Outdoor lighting was not inspected. 4090 - Hvac extension from existing house was not inspected for size accommodation. New water heater is in a new closet without combustion air or a CO detector. Flue and tpr and dryer vent not inspected due to halting inspection. Plumbing for water heater and laundry is not on permit nor inspected. Contractor/owner need to add plumbing and electric service upgrade to permit. Note: original contractor was discharged per owner. Recommend that new licensed general contractor complete the work needed and be present for the final inspection. |
|
| 09/10/2021 | MECHANICAL - FINAL | Cancelled | Canceled by homeowner | |
| 09/01/2021 | MECHANICAL - FINAL | Cancelled | IVRS - RI canceled | |
| 09/01/2021 | MECHANICAL - FINAL | Cancelled | Contractor never called For inspection after I talk to his boss and he said he was going to sew inspection is canceled today |