Permit: T20CM08998

Parcel: 12617269E

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
11/22/2021 MECHANICAL - FINAL Approved Approved.
09/13/2021 MECHANICAL - FINAL Denied De

Inspection was stopped when it became apparent that all trades were incomplete or had deficiencies.
Outdoor lighting was not inspected.
4090 -
Hvac extension from existing house was not inspected for size accommodation.
New water heater is in a new closet without combustion air or a CO detector. Flue and tpr and dryer vent not inspected due to halting inspection.

Plumbing for water heater and laundry is not on permit nor inspected.

Contractor/owner need to add plumbing and electric service upgrade to permit.

Note: original contractor was discharged per owner. Recommend that new licensed general contractor complete the work needed and be present for the final inspection.
09/10/2021 MECHANICAL - FINAL Cancelled Canceled by homeowner
09/01/2021 MECHANICAL - FINAL Cancelled IVRS - RI canceled
09/01/2021 MECHANICAL - FINAL Cancelled Contractor never called For inspection after I talk to his boss and he said he was going to sew inspection is canceled today