Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Canceled
Inspection History: COT - RSME - Mechanical Final
Permit Number - T20CM08404
Inspection Description - COT - RSME - Mechanical Final
Inspection Status - Canceled
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/04/2022 | COT - RSME - Mechanical Final | Canceled | Inspection Canceled | |
02/07/2024 | COT - RSME - Mechanical Final | Re-inspection required | 2/7/24: receptacle under kitchen sink must be GFCI and must be properly installed (currently installed behind cabinet), Arc-fault breaker's missing at multiple locations, outdoor receptacle must be WR, water hammer arrestors missing at dishwasher and laundry room, anti-tip missing at range, kitchen sink and bathroom lavs all have drainage against code (interior must be smooth surface), A/C unit missing p-trap and condensate drain, bathroom and laundry room have been switched (plans must be submitted and show new location), toilets must be caulked. Insulate water lines at water heater. | |
03/08/2024 | COT - RSME - Mechanical Final | Passed |