Inspection Status: Passed
Inspection History: COT - LCME - Kitchen Hood
Permit Number - T20CM08395
Inspection Description - COT - LCME - Kitchen Hood
Inspection Status - Passed
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/10/2021 | COT - LCME - Kitchen Hood | DMUNIZ | Approved | Entered by VVERA1 - Approved |
09/21/2021 | COT - LCME - Kitchen Hood | DMUNIZ | Correction Required | Entered by NGARCIA3 - Corrections required, Smoke test failed @ interconnection points from Hood to grease duct. I am requesting that a different design be applied to this system to meet manufacturers, air flow & slope requirements. |
09/17/2021 | COT - LCME - Kitchen Hood | DMUNIZ | Correction Required | Entered by NGARCIA3 - corrections required, Leak detected on East hood/Duct connection, repair and retest. |
08/18/2021 | COT - LCME - Kitchen Hood | DMUNIZ | Correction Required | Entered by VVERA1 - corrections required, Install steel fabricated interconnection from hood to duct. Provide manufacturer recommended smoke test. Tilt exhaust cap to drain properly. |