Inspection History: COT - LCME - Kitchen Hood

Permit Number - T20CM08395

Inspection Description - COT - LCME - Kitchen Hood

Inspection Status - Passed

Date Description Inspector Results Comments
12/10/2021 COT - LCME - Kitchen Hood DMUNIZ Approved Entered by VVERA1 - Approved
09/21/2021 COT - LCME - Kitchen Hood DMUNIZ Correction Required Entered by NGARCIA3 - Corrections required, Smoke test failed @ interconnection points from Hood to grease duct. I am requesting that a different design be applied to this system to meet manufacturers, air flow & slope requirements.
09/17/2021 COT - LCME - Kitchen Hood DMUNIZ Correction Required Entered by NGARCIA3 - corrections required, Leak detected on East hood/Duct connection, repair and retest.
08/18/2021 COT - LCME - Kitchen Hood DMUNIZ Correction Required Entered by VVERA1 - corrections required, Install steel fabricated interconnection from hood to duct. Provide manufacturer recommended smoke test. Tilt exhaust cap to drain properly.