Inspection Status: Passed
Inspection History: COT - LCME - Kitchen Hood
| Date |
Description |
Inspector |
Results |
Comments |
| 12/10/2021 |
COT - LCME - Kitchen Hood |
DMUNIZ |
Approved |
Entered by VVERA1 - Approved |
| 09/21/2021 |
COT - LCME - Kitchen Hood |
DMUNIZ |
Correction Required |
Entered by NGARCIA3 - Corrections required, Smoke test failed @ interconnection points from Hood to grease duct. I am requesting that a different design be applied to this system to meet manufacturers, air flow & slope requirements. |
| 09/17/2021 |
COT - LCME - Kitchen Hood |
DMUNIZ |
Correction Required |
Entered by NGARCIA3 - corrections required, Leak detected on East hood/Duct connection, repair and retest.
|
| 08/18/2021 |
COT - LCME - Kitchen Hood |
DMUNIZ |
Correction Required |
Entered by VVERA1 - corrections required, Install steel fabricated interconnection from hood to duct. Provide manufacturer recommended smoke test. Tilt exhaust cap to drain properly. |