Permit: T20CM08395

Parcel: Unknown

Inspection Status: Passed

Inspection History: COT - LCME - Mechanical Above Ceiling

Date Description Inspector Results Comments
12/10/2021 COT - LCME - Mechanical Above Ceiling DMUNIZ Approved Entered by VVERA1 - Approved
11/15/2021 COT - LCME - Mechanical Above Ceiling JBURGE Partial Approval Entered by RSALDAT1 - Partial, Smoke test on Hood to Grease duct connection complete ok to fire wrap.
11/05/2021 COT - LCME - Mechanical Above Ceiling DMUNIZ Correction Required Entered by RSALDAT1 - ) corrections required, smoke test on Hood to duct connection failed. Multiple locations where welds are incorrect, repair, re-test and call in inspection when corrections are complete.
11/04/2021 COT - LCME - Mechanical Above Ceiling DMUNIZ Partial Approval Entered by NGARCIA3 - Partial, no inspection required today, contractor rescheduled.see previous notes.
08/18/2021 COT - LCME - Mechanical Above Ceiling DMUNIZ Partial Approval Entered by VVERA1 - PARTIAL, Above ceiling in Office Building 2nd floor inspected. Note: install seismic tie for all mechanical fixtures in acoustic ceiling locations. Check interconnections for all rigid to flex duct connections. Properly band where needed.