Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.
Inspection Status: Passed
Inspection History: COT - LCME - Mechanical Above Ceiling
| Date |
Description |
Inspector |
Results |
Comments |
| 12/10/2021 |
COT - LCME - Mechanical Above Ceiling |
DMUNIZ |
Approved |
Entered by VVERA1 - Approved |
| 11/15/2021 |
COT - LCME - Mechanical Above Ceiling |
JBURGE |
Partial Approval |
Entered by RSALDAT1 - Partial, Smoke test on Hood to Grease duct connection complete ok to fire wrap.
|
| 11/05/2021 |
COT - LCME - Mechanical Above Ceiling |
DMUNIZ |
Correction Required |
Entered by RSALDAT1 - ) corrections required, smoke test on Hood to duct connection failed. Multiple locations where welds are incorrect, repair, re-test and call in inspection when corrections are complete.
|
| 11/04/2021 |
COT - LCME - Mechanical Above Ceiling |
DMUNIZ |
Partial Approval |
Entered by NGARCIA3 - Partial, no inspection required today, contractor rescheduled.see previous notes. |
| 08/18/2021 |
COT - LCME - Mechanical Above Ceiling |
DMUNIZ |
Partial Approval |
Entered by VVERA1 - PARTIAL, Above ceiling in Office Building 2nd floor inspected. Note: install seismic tie for all mechanical fixtures in acoustic ceiling locations. Check interconnections for all rigid to flex duct connections. Properly band where needed. |