Inspection History Details
Inspection Status: Passed
Inspection History: COT - LCME - Mechanical Above Ceiling
Permit Number - T20CM08395
Inspection Description - COT - LCME - Mechanical Above Ceiling
Inspection Status - Passed
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/10/2021 | COT - LCME - Mechanical Above Ceiling | DMUNIZ | Approved | Entered by VVERA1 - Approved |
11/15/2021 | COT - LCME - Mechanical Above Ceiling | JBURGE | Partial Approval | Entered by RSALDAT1 - Partial, Smoke test on Hood to Grease duct connection complete ok to fire wrap. |
11/05/2021 | COT - LCME - Mechanical Above Ceiling | DMUNIZ | Correction Required | Entered by RSALDAT1 - ) corrections required, smoke test on Hood to duct connection failed. Multiple locations where welds are incorrect, repair, re-test and call in inspection when corrections are complete. |
11/04/2021 | COT - LCME - Mechanical Above Ceiling | DMUNIZ | Partial Approval | Entered by NGARCIA3 - Partial, no inspection required today, contractor rescheduled.see previous notes. |
08/18/2021 | COT - LCME - Mechanical Above Ceiling | DMUNIZ | Partial Approval | Entered by VVERA1 - PARTIAL, Above ceiling in Office Building 2nd floor inspected. Note: install seismic tie for all mechanical fixtures in acoustic ceiling locations. Check interconnections for all rigid to flex duct connections. Properly band where needed. |