Permit: T20CM07264

Parcel: 11621305A


Addresses:

902 W CONGRESS ST


Inspection Status: Approved

Inspection History: ELECTRIC - UFER

Permit Number - T20CM07264

Inspection Description - ELECTRIC - UFER

Inspection Status - Approved

Date Description Inspector Results Comments
12/02/2021 ELECTRIC - UFER Approved
08/24/2021 ELECTRIC - UFER Partial Approval Partial. Building #3; ufer and ground rods at disconnect and service panels.
07/28/2021 ELECTRIC - UFER Partial Approval Partial. Ground rods and disconnects for buildings: 6; 6A-6C; 9A; 10; 11A. Switch gear cabinet for building #5.
07/08/2021 ELECTRIC - UFER Partial Approval pa
Rods ok for service 12A and B
06/30/2021 ELECTRIC - UFER Partial Approval Partial. Ufer at Building #12A: 3.0 wiring and 2 ground rods. Ok to cover progress areas.
06/16/2021 ELECTRIC - UFER Partial Approval Partial. Users for services at Buildings 7B; 8; 9A. Ok to cover progress areas.
06/10/2021 ELECTRIC - UFER Partial Approval Partial. Ufers and ground rods for buildings #4; 5; 6; 7 to disconnects.