Inspection History Details
Inspection Status: Passed
Inspection History: COT - HCPL - Sewer
Permit Number - T20CM07013
Inspection Description - COT - HCPL - Sewer
Inspection Status - Passed
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/21/2021 | COT - HCPL - Sewer | DQUINN | Approved | Entered by NGARCIA3 - Ap 6” pvc from manhole to building connection ok to backfill. |
10/20/2021 | COT - HCPL - Sewer | DQUINN | Partial Approval | Entered by VVERA1 - pa Next 40’ of 6” pvc main drain line, ok to backfill. |
10/19/2021 | COT - HCPL - Sewer | JBURGE | Partial Approval | Entered by NGARCIA3 - Partial. Sewer line (6”) on East side of project at 6’ below elevation. Approximately 35’ of trenching. Ok to cover progress. |
10/13/2021 | COT - HCPL - Sewer | DQUINN | Cancelled | Entered by NGARCIA3 - ca Per Willy |
10/12/2021 | COT - HCPL - Sewer | JBURGE | Partial Approval | Entered by VVERA1 - Partial. HCS connection has not been tapped to main sewer line at this point; 6” sewer line in place, approximately 50’ south of proposed HCS tap. Ok to cover progress areas. |
10/13/2021 | COT - HCPL - Sewer | IVR USER | Cancelled | Entered by IVR USER - IVRS - RI canceled |