Inspection History Details
Inspection Status: Approved
Inspection History: RESIDENTIAL INTERMEDIATE
Permit Number - T20CM06859
Inspection Description - RESIDENTIAL INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/08/2021 | RESIDENTIAL INTERMEDIATE | Approved | ||
05/28/2021 | RESIDENTIAL INTERMEDIATE | Partial Approval | PA. 1-Smoke detector in upstairs hallway, and Southwest bedroom are too close to wall. 2-B-vent in garage has less than 1” clearance to combustibles. 3-Floor truss by water heater had been notched; provide engineered repair. |