Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
Permit Number - T20CM06572
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/13/2020 | ELECTRIC - RECONNECT | Approved | Clear rec | |
| 10/12/2020 | ELECTRIC - RECONNECT | Denied | de 1. Sub-panel has over fused fuses. 2. Need all smokies. 3. Correct exposed romex in closet(s). 4. All 3 prong outlets, on the 2 wire system, must be returned to 2 prong outlets or gfi’s marked ungrounded. Note: 5. Breakers/ fuses should be labeled, after power is restored, as to what circuits they protect. |