Permit: T20CM06400

Parcel: 105122050

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
12/31/2020 PLUMBING - FINAL Approved Ap
11/03/2020 PLUMBING - FINAL Denied A pressure relief valve can no longer use flex pipe. A pressure valve must be hard piped with a three-quarter inch pipe only. This pipe also must always be pitched for drainage like any plumbing drain.
10/20/2020 PLUMBING - FINAL Cancelled ca
By Loren. Work not complete.
10/15/2020 PLUMBING - FINAL Partial Approval pa

Need lockout breaker or a disconnect at the unit.