Permit: T20CM06322

Parcel: 13213075A

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
04/08/2021 ELECTRIC - INTERMEDIATE Approved
03/16/2021 ELECTRIC - INTERMEDIATE Partial Approval Partially Approved-PA for Service Entrance requiring TEP Clearance. Please send ECO Clearance to TEP (Lock out main panel if energized )
03/01/2021 ELECTRIC - INTERMEDIATE Partial Approval Partial. Eight light pole caisson footings with rebar spread footings; #5 rebar mat with #6 vertical rebar. Ok to place concrete in progress areas
02/25/2021 ELECTRIC - INTERMEDIATE Partial Approval Partial. In wall electric. Ok to insulate and cover walls.
02/24/2021 ELECTRIC - INTERMEDIATE Not ready for Inspection NOT READY