Inspection History Details
Inspection Status: Not Ready
Inspection History: COT - FCON - Fire - Final
Permit Number - T20CM05674
Inspection Description - COT - FCON - Fire - Final
Inspection Status - Not Ready
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
COT - FCON - Fire - Final | Not Ready | Exit signs above exit doors need to be repaired, Fire sprinklers need to be evaluated by a licensed fire sprinkler contractor. | ||
06/05/2024 | COT - FCON - Fire - Final | Partial Pass | North exit sign (near restroom sign) needs to be repaired. Ok to obtain TCO level 4. | |
03/26/2024 | COT - FCON - Fire - Final | Re-inspection required (with fee) | All ceiling tiles shall be in place. Provide illuminated exit sign over south hall exit. Remove ceiling where it would obstruct upright coverage. Remove pendant in area protected by uprights. East door shall open with <15 pounds of force. Defunct alarm equipment shall be removed. | |
06/05/2024 | COT - FCON - Fire - Final | Passed |