Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T20CM05644
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/13/2022 | MECHANICAL - FINAL | Approved | AP. No access to inspection records. | |
| 09/08/2022 | MECHANICAL - FINAL | Partial Approval | REVIEW OF AIR BALANCE REPORT COMPLETED | |
| 06/06/2022 | MECHANICAL - FINAL | Correction Required | BALANCE REPORT TO BE REVIEWED BY ENGINEER - AC-7 TOTAL FLOW 49% LOW, EF-16 FLOW 16% LOW | |
| 05/25/2022 | MECHANICAL - FINAL | Denied | DE. 1-B vents need insulation shields. 2-Provide ladders at walls higher than 30” around roof top equipment where roof hatch does not allow direct access. 3-Mechanical exhausts are less than 10’ from air intakes. 4-Secure mechanical disconnects. | |
| 05/13/2022 | MECHANICAL - FINAL | Partial Approval | PA. Recommend TCO upon approval of chlorination report. |