Permit: T20CM05644

Parcel: 12807280B


Addresses:

730 S WILMOT RD

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/13/2022 MECHANICAL - FINAL Approved AP. No access to inspection records.
09/08/2022 MECHANICAL - FINAL Partial Approval REVIEW OF AIR BALANCE REPORT COMPLETED
06/06/2022 MECHANICAL - FINAL Correction Required BALANCE REPORT TO BE REVIEWED BY ENGINEER - AC-7 TOTAL FLOW 49% LOW, EF-16 FLOW 16% LOW
05/25/2022 MECHANICAL - FINAL Denied DE. 1-B vents need insulation shields. 2-Provide ladders at walls higher than 30” around roof top equipment where roof hatch does not allow direct access. 3-Mechanical exhausts are less than 10’ from air intakes. 4-Secure mechanical disconnects.
05/13/2022 MECHANICAL - FINAL Partial Approval PA. Recommend TCO upon approval of chlorination report.