Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/13/2022 |
MECHANICAL - FINAL |
|
Approved |
AP. No access to inspection records. |
| 09/08/2022 |
MECHANICAL - FINAL |
|
Partial Approval |
REVIEW OF AIR BALANCE REPORT COMPLETED |
| 06/06/2022 |
MECHANICAL - FINAL |
|
Correction Required |
BALANCE REPORT TO BE REVIEWED BY ENGINEER - AC-7 TOTAL FLOW 49% LOW, EF-16 FLOW 16% LOW |
| 05/25/2022 |
MECHANICAL - FINAL |
|
Denied |
DE. 1-B vents need insulation shields. 2-Provide ladders at walls higher than 30” around roof top equipment where roof hatch does not allow direct access. 3-Mechanical exhausts are less than 10’ from air intakes. 4-Secure mechanical disconnects. |
| 05/13/2022 |
MECHANICAL - FINAL |
|
Partial Approval |
PA. Recommend TCO upon approval of chlorination report. |