Permit: T20CM05391

Parcel: 13337017F


Addresses:

10315 E BROADWAY BL


Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T20CM05391

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/16/2020 FIRE - FINAL Approved -Post "FACP" on outer doors to the fire alarm control panel.
11/09/2020 FIRE - FINAL Partial Approval Ok to obtain TCO through the building department
-Need to establish a Fire Watch 24hrs a day until the fire alarm is complete.
-Need to install a knox box near the main entrance.
11/06/2020 FIRE - FINAL Prior to Final Inspectn Still needs a full fire final inspection
11/06/2020 FIRE - FINAL Prior to Final Inspectn NEEDS TO FINAL ALARM PERMIT. OK TO HAVE FIRE WATCH 24HRS/DAY FOR TCO IF TCO IS APPROVED BY INSPECTOR. OBTAIN TCO FROM PDSD.
11/04/2020 FIRE - FINAL Prior to Final Inspectn 1. Need to have a knox box installed near the main entrance.
2..Need knox cap lock for sprinkler connection.
3. Need to have a sign on the fire alarm room door. FACP red.